BS EN 62041-2010 pdf download

08-08-2021 comment

BS EN 62041-2010 pdf download.Safety of transformers, reactors, power supply units and combinations thereof
EMC requirements.
3.7
signal port
port at which a conductor or cable intended to carry signals Is connected to the EUT
NOTE Examples are analogue Inputs, outputs and control lines, data busses, communication networks, etc.
3.8
power port
port at which a conductor or cable carrying the primary electrical power needed for the operation (functioning) of an EUT is connected
3.9
public mains network
power lines to which all categories of consumers have access to and that are operated by an electrical power supply and/or distribution organization for the purpose of supplying electrical energy
3.10
long distance lines
lines connected to a signal port and which inside a building are longer than 30 m, or which leave the building (including lines of outdoor installations)
low voltage
voltage having a value below a conventionally adopted limit
[IEC 60050-151:2001. 151-15-03]
4 Classification
EUT are classified according to the incorporation of components and electronic circuits as follows:
— category 0: EUT with or without passive protection component(s) and without electronic circuits:
— category 1: EUT with passive components, and without electronic circuits:
— category 2: EUT with electronic circuits.
NOTE I Examples of passive protection components are fuses, thermal links, thermal cut-outs, circuit-breakers, PTC’s, NTC’s and resistors.
NOTE 2 Examples of pas5ive components are capacitors, inductors, diodes, LED’s, relays. VDR’s.
— electrostatic discharge:
— electrical fast transientlburst:
— surge:
— conducted disturbances, inducted by radio-frequency fields:
— radiated, radio-frequency electromagnetic fields:
— voltage dips and short interruptions.
The requirements are given In 5.1.2.2 to 5.1.2.7 on a port-by-port basis.
The relevant ports of the EUT shall be subjected to the required test in accordance with the applicable subclauses. Tests shall be carried out only when the relevant ports exist.
Tests shall be conducted under the no-load condition at the rated voltage and the rated frequency. unless otherwise specified in the generic EMC standard as indicated in Clause 5. If EUT is not intended to operate under the no load condition, for some tests, a load may need to be applied for perturbation. In this case, the specification of the load shall be stated in the test report.
Tests shall be conducted sequentially. The sequence of testing is optional.
The necessity to conduct some of the tests may be determined in accordance with the electrical characteristics and the specific application of the particular transformer. In such cases the rationale for not conducting the tests shall be stated in the test report.
The description of the tests, the test generator, the test methods and the test set-up are specified in the generic EMC standard for testing in accordance with Clause 5.
The tests are carried out following the manufacturer’s documentation. This includes a functional description and explanation of performance criteria, during or as a consequence of the EMC testing. This shall be provided by the manufacturer and included in the test report, based on the following criteria. In case of no documentation, necessary conductors, the cross section, the type and the length of the conductors used shall be reported in the test report.
Performance criterion A: The EUT shall continue to operate as intended during and after the test. No degradation of performance or loss of function Is allowed below a performance level specified by the manufacturer, when the EUT is used as intended. The performance level may be replaced by a permissible loss of performance. If the minimum performance level or the permissible performance loss is not specified by the manufacturer, either of these may be derived from the product description and documentation and what the user may reasonably expect from the EUT if used as intended.
Performance criterion B: The EUT shall continue to operate as intended after the test. No degradation of performance or loss of function Is allowed below a performance level specified by the manufacturer, when the EUT is used as intended. The performance level may be replaced by a permissible loss of performance. During the test, degradation of performance Is, however, allowed. No change of actual operating state or stored data is allowed. If the minimum performance level or the permissible performance loss is not specified by the manufacturer, either of these may be derived from the product description and documentation and what the user may reasonably expect from the EUT if used as intended.
Performance criterion C: Temporary loss of function is allowed, provided the function is self- recoverable or can be restored by the operation of the controls.
If, as a result of the application of the tests defined in this standard, the transformer becomes dangerous or unsafe (e.g., by an Insulation breakdown), the EUT Is deemed to have failed the tests.
5.1.2 Test levels
5.1.2.1 General
Levels for test stated in this standard correspond to typical condition for environment I and 2. However, if special conditions prevail for the use of the final product, the relevant values in the basic standard shall be applied and stated in the test report.
5.1.2.2 Electrostatic discharges
These tests are carried out according to IEC 61000-4-2, with test levels as given in Table 1,
Except for metallic parts for which a contact discharge test is made, only air discharge test is required.
Ten positive and ten negative pulses shall be applied to each selected point. The time interval between each successive single discharge is 1 s.BS EN 62041-2010 pdf download.

                                           Related Information                                             Download
PS:Thank you for your support!
BS EN 12607-3-2000 pdf download BS Standards

BS EN 12607-3-2000 pdf download

BS EN 12607-3-2000 pdf download.Methods of test for petroleum and its products — BS 2000-460.3: Bitumen and bituminous binders — Determination of the resistance to hardening under the influence of heat and air — Part 3: RFT...
Read More
EN 12329-2000 pdf download BS Standards

EN 12329-2000 pdf download

BS EN 12329-2000 pdf download.Corrosion protection of metals — Electrodeposited coatings of zinc with supplementary treatment on iron or steel. This BS EN 12329 specifies requirements for electrodeposited coatings of zinc on iron or steel witt supplementary...
Read More
BS EN 1430-2000 pdf download BS Standards

BS EN 1430-2000 pdf download

BS EN 1430-2000 pdf download.Methods of test for petroleum and its products — BS 2000-292:Bitumen and bituminous binders — Determination of particle polarity of bitumen emulsions (Identical with IP 292-2000). This BS EN 1430 specifies a method...
Read More

LEAVE A REPLY

Anonymous netizen Fill in information