AS IEC 62053.31:2018 pdf download – Pulse output devices

07-08-2021 comment

AS IEC 62053.31:2018 pdf download.Electricity metering equipment (a.c.)-Particular requirements Part 31: Pulse output devices for electromechanical and electronic meters (two wires only).
4 Requirements
Meters equipped w ith pulse output devic es shall comply with all the r equirements of the relevant meter standard, unless otherwise specified in the present standard.
4.1 Functional requirements
4.1.1 Introduction The output pulse is characterized by two states: ON-state and OFF-state, as defined in table 1. Each ON-state and each OFF-state is followed by a transient state before reaching the other state. Two types of pulse output devices are defined in this standard: — pulse output devices class A for long range transmission; — pulse output devices class B for short range and low power consumption. The pulse output shall generate a number of pulses proportional to the measured energy.
4.1.2 Electrical environment The physical interface of the pulse output device is described in annex A. The supply source for the output circuit shall originate from an external device (e.g. multi-rate unit) or other selected source.
4.1.3 Pulse characteristics 4.1.3.1 Output pulse waveform The pulses shall have the shape shown in figure B.1.
4.1.3.2 Supply polarity When the m eter is equipped w ith several pulse outputs that have a common terminal this common terminal shall be negative.
4.1.3.3 Pulse duration The pulse duration tON is defined in figure B.1 with tON ≥ 30 ms. The time between two successive pulses tQFF is defined in figure B.1 with tOFF  ≥ 30 ms.
4.1.3.4 Transition time (tT) The transition time (rise time or fall time) is the tim e from one s tate to the other , including transient effects, e.g. contact bounce. The transition time shall be less than 5 ms (see figure B.1).
4.2 Mechanical requirements 4.2.1 General The features of the pulse device shall comply with all mechanical requirements stated in the standard applying to the meter in which it is included. Refer to the appropriate standard.
4.2.2 Marking of the pulse value Information on the pulse value in the form x (energy units)/imp or X imp/(energy units) shall be added on the meter name plate or on a separate plate (imp = pulse).
4.3 Climatic conditions Refer to IEC 61036.
4.4 Electrical requirements
4.4.1 Interaction with the meter In order to ascertain that the pulse output device has no adverse influence on the meter and the meter has no adver se influence on the puls e output device, the tests of the following clauses and subclauses shall be carried out and the r equirements met, unless otherwise specified in this standard: — clause 6 “Electrical requirements” and clause 8 “Accuracy” of IEC 60145; — clause 6 “Electrical requirements”, clause 8 “Accuracy”, clause 9 “Starting and running with no load” and clause 10 “Adjustment” of IEC 60521; — subclauses 4.4 “Electrical requirements” and 4.6 “Accuracy requirements” of IEC 60687, IEC 61036 and IEC 61268.
4.4.2 Power consumption For static meters and electromechanical meters equipped with pulse output devices, the power consumption shall not exceed the values specified in table 1 of IEC 61899 for multi-function meters.
4.4.3 Influence of supply voltage
4.4.3.1 Voltage range Refer to IEC 61036.
4.4.3.2 Voltage dips and short interruptions Voltage dips and short interruptions shall not cause more than one pulse. When the voltage is restored the pulse output device shall not have suffered degradation of its characteristics. For testing see 5.4.1.
4.4.4 Insulation The pulse output device shall withstand the impulse voltage test and the a.c. voltage test, as specified in 5.4.6 of IEC 61036.
4.5 Electromagnetic compatibility (EMC)
4.5.1 Immunity to electromagnetic disturbance The pulse output devic e shall be des igned in s uch a w ay that conducted or radiated electromagnetic disturbance as well as electrostatic discharge do not dam age or substantially influence the pulse output device or the meter in which it is included. For testing see 5.5.1 to 5.5.4.
4.5.2 SuppressIon of radio Interference Meters equipped with pulse output devic es shall not gener ate conducted or radiated noise which can interfere with other equipment.
For testing, see 5.5.5.AS IEC 62053.31 pdf download.

                                           Related Information                                             Download
PS:Thank you for your support!
AS NZS 60335.2.52:2018 AS Standards

AS NZS 60335.2.52:2018

AS NZS 60335.2.52:2018 pdf download.Household and similar electrical appliances—Safety Part 2.52: Particular requirements for oral hygiene appliances. 2 Normative references This clause of Part 1 is applicable except as follows. Addition: IEC 60584-1, Thermocouples — Part 1:...
Read More

LEAVE A REPLY

Anonymous netizen Fill in information