IEEE 1692-2011 pdf download

01-14-2023 comment

IEEE 1692-2011 pdf download IEEE Guide for the Protection of Commu nication Instal lations from Lightning Effects
High differential eroundgrounds make the powerservice conductors a favored discharge path for LGPR currents.Soil conditions have a significant effect ondifferential ground potentials. Higher soil resistivity will result in higher differential ground potentials fromlightning strikes to earth. With cloud to ground electric potentials in the magnitude of tens of millions ofvolts, an earth strike can be characterized as a current source. When the stroke discharge occurs the currenttraveling in the earth will flow regardless of the soil impedance. General application of ohm’s law wilindicate the higher soil resistivity will result in a higher differential ground potential for a given dischargecurrent.
Sites without towers may experience LGPR effects as much, if not more, than sites with towers as they areess likely to have extensive grounding infrastructure. Sites at most risk are areas with a higher occurrenceof lightning and high soil resistivity.
5.1 Surge protective devices (SPD) and wire-line
The standard surge protective devices (SPD) in the telecommunications industry, for the termination ofcommunication wire-line services is the gas discharge tube (GDT). GDTs are also called gas tubes. GDTscan be found on virtually every telephone pair terminated in homes, buildings. and similar locations. GDTsare designed to shunt most current to ground. If the magnitude shunted does not exceed a certain thresholdthe SPD will help protect equipment, and personnel, from harm
Most shunting devices. however, do not fully protect network clectronic equipment from a GPR or”outgoing current, whether induced from lightning or from a faulted power line. When shunting devicesare connected to an elevated ground (outgoing current) during a GPR event, they merely offer an additionacurrent path off the site to remote earth (the other end).
When SPDs (GDTs, MOVs, ABDs, SCRs, SADs, SASs, etc.) are used as ground shunting devices, theywill not protect equipment from GPR. These devices merely offer an additional path to remote earththrough the communication pairs for any and all outgoing currents
When there is a GPR event the SPD provides a connection of the communication path in the reversedirection from which they were intended to operate and increases the possibility of equipment damage totelcphone and power installations.
The most susceptible locations are those where the equipment is located near, or under, towers and/or areocated at a higher altitude than the surrounding area.
Some of the susceptible locations to equipment damages include the Public Safety Answering Pointlocations (also called 911 PSAP). The typical 911 PSAP center is a relatively small building under, or near.a radio tower. This tower is a likely target for lightning. Personnel taking emergency calls coming into thPSAP may be at a higher risk since they must be at the phones at all times and cannot be off the phoncsduring lightning storms, as recommended in virtually every telephone book in the United States. Foradditional information see ATIS 0600321[B2].
Whether the site is a 911 PSAP center or a cellular telephone (radio) antenna on top of a mountain, speciaprotection methods are available and must be used to reduce the risk of lightning damage to equipment andassociated working personnel. Methods will be presented in this Guide to enable engineers to incorporatethem into the general construction design
Effective protection of sensitive equipment with SPD shunting devices is complex. A well-designedinstallation requires coordination of the protection for low-voltage power feeds (ac and dc) with thprotection for telecommunications facilities in order to minimize the effect of intrabuilding GPR The useof secondary SPD is recommended to supplement the primary SPD (see ITU-T K.11 (B26)). Surgresistibility and impedance of the terminal equipment must be compatible with the selected primary SPD

                                           Related Information                                             Download
PS:Thank you for your support!
IEEE C63.19-2011 pdf download IEEE Standards

IEEE C63.19-2011 pdf download

IEEE C63.19-2011 pdf download American National Standard Methods of Measurement of Compatibility between Wireless Communications Devices and Hearing Aids .3 Organization and use of the standard These technical requirements specify the measurement methods and categorical levels to...
Read More
IEEE 1609-4-2011 pdf download IEEE Standards

IEEE 1609-4-2011 pdf download

IEEE 1609-4-2011 pdf download IEEE Standard for Wireless Access in Vehicular Environments (WAVE)— Multi-channel Operation control channel (CCH) interval: A specified periodic interval of time with respect to CoordinatedUniversal Time (UTC). During the CCH interval a device...
Read More
IEEE 1725-2012 pdf download IEEE Standards

IEEE 1725-2012 pdf download

IEEE 1725-2012 pdf download IEEE Standard for Rechargeable Batteries for Cellular Telephones 3. Definitions For the purposes of this document, the following terms and definitions apply. The IEEE StandardsDictionary: Glossary of Terms & Definitions should be consulted...
Read More

LEAVE A REPLY

Anonymous netizen Fill in information